Connect/Gateway panel guide: Electro Detectors Zerio Plus

Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 core screened data cable

  • Panel RS232 printer port (supplied by Electro Detectors)

  • Nimbus enabled firmware (supplied by Electro Detectors)

Panel configuration

  1. The communications port should be enabled and configured to print events. See the panel manufacturer manual for details.

  2. Depending on the Panel Firmware, you may need to enable the Nimbus Output.

    1. Systems Setup

    2. Edit Panel

    3. Panel Options

    4. System Options

    5. Scroll right and enable 'Nimbus'

Wiring

Using 3 core screened data cable, wire as follows:

Panel RS232 Nimbus RS232
Gr Ground
Out Rx
In Tx



Additional event types

  • VFY FAULT

    • Lost communication with device, low battery or poor signal
  • BATT LOW
    • Low battery - its recommended to change within 60 days
  • BATTERY FAULT 
    • Battery critical