Connect/Gateway panel guide: Electro Detectors Zerio Plus
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 core screened data cable
-
Panel RS232 printer port (supplied by Electro Detectors)
-
Nimbus enabled firmware (supplied by Electro Detectors)
Panel configuration
-
The communications port should be enabled and configured to print events. See the panel manufacturer manual for details.
-
Depending on the Panel Firmware, you may need to enable the Nimbus Output.
-
Systems Setup
-
Edit Panel
-
Panel Options
-
System Options
-
Scroll right and enable 'Nimbus'
-
Wiring
Using 3 core screened data cable, wire as follows:
Panel RS232 | Nimbus RS232 |
Gr | Ground |
Out | Rx |
In | Tx |
Additional event types
-
VFY FAULT
- Lost communication with device, low battery or poor signal
- BATT LOW
- Low battery - its recommended to change within 60 days
- BATTERY FAULT
- Battery critical