Connect/Gateway panel guide: EMS Firecell 8000

Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 core screened data cable

  • A Nimbus supplied Kentec Syncro/EMS FireCell panel connector (part no 201-301-02)

Panel configuration

Set the panels baud rate to 19200 and frame to 8N1.

Wiring

Connect the 10 way IDC connector on the Kentec Syncro/EMS FireCell panel connector to the PC port on the panel.

Using 3 core screened data cable wire to the Nimbus RS232 as follows.

Panel connector Nimbus RS232
Ground Ground
Rx Tx
Tx Rx