Connect/Gateway panel guide: EMS IRIS+
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 Core Screened Data cable
Panel configuration
The IRIS should be configured with a pager output.
To configure:
- Enter the main menu
- Navigate to "Pager Setup" and select "Add Pager"
- Enter an appropriate "Pager ID"
- Under Pager Type, select "Alpha - 80"
- Under Buzzer Type, select "Buzzer A"
- Once the Pager is added, select Transmitter Setup and change Type from "Not Used" to "A-Type"
Wiring
Using 3 core screened data cable wire from the page RS232 to Nimbus as follows.
Pager RS232 | Nimbus RS232 |
Tx | Rx |
0V | Ground |
Rx | Tx |
A connection may be required, on the IRIS pager port, between CTS and DTR.