Connect/Gateway panel guide: EMS IRIS+

Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 Core Screened Data cable

Panel configuration

The IRIS should be configured with a pager output.

To configure:

  1. Enter the main menu
  2. Navigate to "Pager Setup" and select "Add Pager"
  3. Enter an appropriate "Pager ID"



  4. Under Pager Type, select "Alpha - 80"



  5. Under Buzzer Type, select "Buzzer A"



  6. Once the Pager is added, select Transmitter Setup and change Type from "Not Used" to "A-Type"



Wiring

Using 3 core screened data cable wire from the page RS232 to Nimbus as follows.

Pager RS232 Nimbus RS232
Tx Rx
0V Ground
Rx Tx

 

 

 

A connection may be required, on the IRIS pager port, between CTS and DTR.