Connect/Gateway panel guide: Fike Twinflex
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 core screened data cable
-
USB A to USB A cable
-
A Nimbus supplied Fike Twinflex panel connector (part no 201-308-01)
Panel configuration
Set the panels baud rate to 9600 and frame to 8N1.
Wiring
Connect the interface to the panel via USB. The USB to RS232 interface is usually mounted close to the fire panel, on a single gang electrical accessory pattress box. Power to the Interface is usually supplied from the panel.
Using 3 core screened data cable wire to the Nimbus RS232 as follows.
Panel connector | Nimbus RS232 |
Gnd | Ground |
Rx | Tx |
Tx | Rx |