Connect/Gateway panel guide: Morley ZX

Overview

Nimbus supports connection to either the Morley RS232 card or the mainboard programming header.

Networks

In network configurations, the physical connection between Nimbus Gateway and Panel, should be made to the ‘Master Panel’.

Each Morley panel has its own node number in a networked system. The node number of the panel that is connected to the Nimbus device must be entered in the Node Number text field on the Nimbus Web Portal, under the equipment settings.



Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 core screened data cable

AND

  • Morley EXP-005 (Port ‘B’) RS232 card

OR

  • A Nimbus Morley ZX panel connector (part no 201-306-01)

Panel configuration

  1. If required, install the Morley EXP-005 (Port ‘B’) RS232 card according to the manufacturers instructions.

  2. Configure the panel:

    1. Press [Menu

    2. Select option [6 Print]

    3. Select option [3 Mode]

    4. Select option [ - ]

  1. Set the baud rate to 9600 and the frame to 8N1.

Note: the panel will not output events to Nimbus while in commissioning mode.

Wiring

Morley EXP-005 (Port ‘B’) RS232 card

Using 3 core screened data cable wire to the Nimbus RS232 as follows.

RS232 card Nimbus RS232
Rx Tx
Tx Rx
0V Ground


Mainboard programming header

Connect the Morley ZX panel connector to the programming header. Using 3 core screened data cable wire to the Nimbus RS232 as follows.

Panel connector Nimbus RS232
0V Ground
Rx Tx
Tx Rx