Connect/Gateway panel guide: Notifier Pearl
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 core screened data cable
-
Notifier Pearl RS232 & RS485 Communication Card Kit (Part No. PRL-COM)
Panel configuration
-
Install the Pearl Communication Card Kit according to the manufacturers instructions.
- Configure the panel
- From the Panel Main Menu, Select the "Commissioning Tab" and input the Commissioning passcode to access the "Commission Menu"
- Select "Edit Configuration
- Select "Panel Configuration"
- Select "Plug-in Card Option"
- Select either "Plug-in Comms Card A Options" (if the Card is installed in the left hand position) or "Plug-in Comms Card B options" (if the Card is installed in the right hand position).
- Set the card options:
- Card Present : YES
- Card Address : As per rotary switch on card
- RS232 Protocol : TPP011A
- RS232 Baud Rate: 9600
- RS232 Comms Mode : FULL
- RS232 Datalink Mon: DISABLED
- RS232 Suspend Limit: 0
- RS232 Panel Control: PREVENT
- All Other Card Settings left as Default, with RS485 Protocol for this card Disabled.
Wiring
Using 3 core screened data cable wire to the Nimbus RS232 as follows.
Communication Card RS232 port | Nimbus RS232 |
Tx | Rx |
Rx | Tx |
Grd | Ground |