Connect/Gateway panel guide: Tyco Fireclass/MX/MZX/Zettler
Equipment required
From Nimbus
- A Nimbus Connect or Fixed Gateway device
- A Tyco MX/MZX/Fireclass panel connector (part no 201-303-02)
From the panel manufacturer/3rd party
- Screened data cable
- Consys v25.0 or later
Panel configuration
- Set the panel baud rate to 9600
- Set Comm Port 1 to Printer or TPI mode
- When configured as a printer, comm 1 outputs 2 lines of ASCII data
- When configured as a TPI, comm port 1 outputs 3 lines of ASCII data
- Ensure Paper Width is set to Standard (80)
- Enable Quiescent Logging
The configured mode must match that of the equipment in the Nimbus Web Portal to enable communications.
Note that TPI mode includes a heartbeat to enable communications path monitoring.
Wiring
- Connect the Tyco MX/MZX/Fireclass panel connector to Comm Port 1
- Using screened data cable wire to the Nimbus RS232 as follows
| Panel connector | Nimbus RS232 |
| Ground | Ground |
| Tx | Rx |