Connect/Gateway panel guide: Tyco Fireclass/MX/MZX/Zettler
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 core screened data cable
-
A Nimbus supplied Tyco MX/MZX/Fireclass panel connector (part no 201-303-02)
- Consys v25.0 or later
Panel configuration
- Set the panel baud rate to 4800
- Set Comm Port 1 to Printer or TPI mode
- When configured as a printer, comm 1 outputs 2 lines of ASCII data
- When configured as a TPI, comm port 1 outputs 3 lines of ASCII data.
The configured mode must match that of the equipment in the Nimbus Web Portal to enable communications.
Wiring
Connect the Tyco MX/MZX/Fireclass panel connector to comm port 1.
Using screened data cable wire to the Nimbus RS232 as follows.
Panel connector | Nimbus RS232 |
Ground | Ground |
Rx | Tx |