Connect/Gateway panel guide: Kentec Syncro AS/XT+
Equipment required
-
A Nimbus Connect or Fixed Gateway device
-
3 core screened data cable
-
Nimbus supplied Kentec Syncro/EMS FireCell panel connector (part no 201-301-02)
Panel configuration
Set the panels baud rate to 19200 and frame to 8N1.
Wiring
Connect the 10 way IDC connector on the Kentec Syncro/EMS FireCell panel connector to the PC port on the panel.
Using 3 core screened data cable wire to the Nimbus RS232 as follows.
Panel connector | Nimbus RS232 |
Ground | Ground |
Rx | Rx |
Tx | Rx |