Connect/Gateway panel guide: Morley DX Connexion

Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 core screened data cable

  • A Morley DXc RS232 card

Panel configuration

  1. Install the Morley DXc RS232 card according to the manufacturers instructions

  2. Configure the panel

    1. Press [OK

    2. Select [5 Action]

    3. Enter Level 3 password

    4. Select [7 Commission Menu]

    5. Press [OK]

    6. Select [1 General]

    7. Select [2nd Serial Port]

    8. Serial Port Settings:

      1. Set Serial Port to [TPP]

      2. Set Baud to [9600]

      3. Set Monitor Link to [No]

      4. Set Remote Control to [No]

Wiring

Using 3 core screened data cable wire to the Nimbus RS232 as follows.

RS232 card Nimbus RS232
0V Ground
Tx Rx
Rx Tx