Connect/Gateway panel guide: Notifier Pearl

Equipment required

  • A Nimbus Connect or Fixed Gateway device

  • 3 core screened data cable

  • Notifier Pearl RS232 & RS485 Communication Card Kit (Part No. PRL-COM)

Panel configuration

  1. Install the Pearl Communication Card Kit according to the manufacturers instructions.

    1. Configure the panel
      1. From the Panel Main Menu, Select the "Commissioning Tab" and input the Commissioning passcode to access the "Commission Menu"
      2. Select "Edit Configuration
      3. Select "Panel Configuration"
      4. Select "Plug-in Card Option"
      5. Select either "Plug-in Comms Card A Options" (if the Card is installed in the left hand position) or "Plug-in Comms Card B options" (if the Card is installed in the right hand position).
      6. Set the card options:
        1. Card Present : YES
        2. Card Address : As per rotary switch on card
        3. RS232 Protocol : TPP011A
        4. RS232 Baud Rate: 9600
        5. RS232 Comms Mode : FULL
        6. RS232 Datalink Mon: DISABLED
        7. RS232 Suspend Limit: 0
        8. RS232 Panel Control: PREVENT
        9. All Other Card Settings left as Default, with RS485 Protocol for this card Disabled.



    Wiring

    Using 3 core screened data cable wire to the Nimbus RS232 as follows.

    Communication Card RS232 port Nimbus RS232
    Tx Rx
    Rx Tx
    Grd Ground