nimbusGo panel guide: Edwards EST3
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (TX, RX, GND) Panel Adapter (part no 201-104-01).
From the panel manufacturer/3rd party
- n/a
Panel configuration
Set the panels baud rate to 9600 and frame to 8N1.
Panel connections
Connect nimbusGo to the RS232 connections on the interface via the 2m Adapter Lead and Multi Panel (TX, RX, GND) Panel Adapter, wired as below.
Panel RS232 | Multi Panel (TX, RX, GND) Panel Adapter |
COM1/COM2 | Ground |
Tx1/Tx2 | Rx |
Rx1/Rx2 | Tx |
Trigger an event to initialise the communications. You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer