nimbusGo panel guide: Electro Detectors Zerio Plus
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (TX, RX, GND) Panel Adapter (part no 201-104-01).
From the panel manufacturer/3rd party
- Nimbus enabled firmware.
Panel configuration
Depending on the panel firmware, you may need to enable the Nimbus output.
- Systems Setup
- Edit Panel
- Panel Options
- System Options
- Scroll right and enable 'Nimbus'.
Panel connections
Connect nimbusGo to the RS232 card via the 2m Adapter Lead and the Multi Panel (TX, RX, GND) Panel Adapter.
Trigger an event to initialise the connection. You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer