nimbusGo panel guide: EMS Firecell 8000

Equipment required

From Nimbus

From the panel manufacturer/3rd party

  • n/a

 

Panel configuration

Set the panels baud rate to 19200 and frame to 8N1.

 

Panel connections

Connect nimbusGo to the PC port at the front of the panel via the 2m Adapter Lead and Kentec Syncro/Taktis Panel Adapter.

You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.

Should this not show green after a few seconds, you may need to restart the panel to initialise communication.