nimbusGo panel guide: EMS IRIS+
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (TX, RX, GND) Panel Adapter (part no 201-104-01).
From the panel manufacturer/3rd party
- n/a
Panel configuration
The IRIS should be configured with a pager output. To configure, enter the Main Menu:
- Navigate to "Pager Setup" and select "Add Pager".
- Enter an appropriate "Pager ID".
- Under Pager Type, select "Alpha - 80".
- Under Buzzer Type, select "Buzzer A".
- Once the Pager is added, select Transmitter Setup and change Type from "Not Used" to "A-Type".
Panel connections
Connect nimbusGo to the IRIS pager port card, between CTS and DTR, via the 2m Adapter Lead and the Multi Panel (TX, RX, GND) Panel Adapter.
You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer