nimbusGo panel guide: EMS IRIS+

Equipment required

From Nimbus

From the panel manufacturer/3rd party

  • n/a


Panel configuration

The IRIS should be configured with a pager output. To configure, enter the Main Menu:

  1. Navigate to "Pager Setup" and select "Add Pager".
  2. Enter an appropriate "Pager ID".

  3. Under Pager Type, select "Alpha - 80".

  4. Under Buzzer Type, select "Buzzer A".

  5. Once the Pager is added, select Transmitter Setup and change Type from "Not Used" to "A-Type".

 

Panel connections

Connect nimbusGo to the IRIS pager port card, between CTS and DTR, via the 2m Adapter Lead and the Multi Panel (TX, RX, GND) Panel Adapter.

You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.