nimbusGo panel guide: Morley DX Connexion
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (TX, RX, GND) Panel Adapter (part no 201-104-01).
From the panel manufacturer/3rd party
- A Morley DXc RS232 card.
Panel configuration
-
Install the Morley DXc RS232 card according to the manufacturers instructions
-
Configure the panel
-
Press [OK]
-
Select [5 Action]
-
Enter Level 3 password
-
Select [7 Commission Menu]
-
Press [OK]
-
Select [1 General]
-
Select [2nd Serial Port]
-
Serial Port Settings:
-
Set Serial Port to [TPP]
-
Set Baud to [9600]
-
Set Monitor Link to [No]
-
Set Remote Control to [No]
-
-
Panel connection
Connect nimbusGo to the RS232 card via the 2m Adapter Lead and the Multi Panel (TX, RX, GND) Panel Adapter.
You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer