nimbusGo panel guide: Notifier ID2000
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (9 Pin D Male) Panel Adapter (part no 201-102-01).
From the panel manufacturer/3rd party
- n/a.
Panel configuration
- 'High access' code is required to access menus
- Press option 4 followed by 3 (quickly). This opens a hidden menu called “temporary systems options”
- Cycle through the menu by pressing the 'tick' button until you arrive at “diagnostic RS232 port”
- Select option 2 (3rd Party RS232), followed by 'tick'
- Confirm Baud rate at 9600 (default)
- For “3rd party RS232", select option 0 (Neither). This removes the fault monitoring.
- For "3rd Party RS232: Incoming Data Timeout" select 20.
Note: Protocol 011A is not available on the ID2000.
Panel connections
Connect nimbusGo to the RS232 connections on the interface via the 2m Adapter Lead and Multi Panel (9 Pin D Male) Panel Adapter.
You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer
If Nimbus appears to be recording each event 10 times, check the connection between nimbusGo and Panel, specifically the nimbusGo TX to Panel RX.
A poor connection will result in the acknowledgement from the nimbusGo to Panel not being received and 10 copies of each event being reported.