nimbusGo panel guide: Notifier ID60
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Engineer App.
- A 2M Adapter Lead (part no 201-101-01).
- A Multi Panel (9 Pin D Male) Panel Adapter (part no 201-102-01).
From the panel manufacturer/3rd party
- n/a.
Panel configuration
- User Menu > option 6 Enter level 3 password
- User Menu > Configuration > option 6 Panel Settings > option 18 Main board RS232 port settings
- Select type: 3rd Party RS232
- Set Baud rate: 9600
- Set Protocol Version: 011A Protocol
- Set Port Setup: Full Duplex
- Set Controls: Disabled
- Set Fault Monitoring: Disabled
- Set Suspend time limit: 0 & Not logged
- Set Incoming data timeout: 1 second
- Set Allow time sync from 3rd party: No
The panel may buffer events, sending these to nimbusGo when the device is connected. To avoid this, either wait for buffered events to download before beginning the service visit (to avoid devices being marked as passed), or revert the protocol to none following your visit.
Panel connections
Connect nimbusGo to the RS232 connections on the interface via the 2m Adapter Lead and Multi Panel (9 Pin D Male) Panel Adapter.
You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.
Learn more: Servicing equipment with Nimbus Engineer
If Nimbus appears to be recording each event 10 times, check the connection between nimbusGo and Panel, specifically the nimbusGo TX to Panel RX.
A poor connection will result in the acknowledgement from the nimbusGo to Panel not being received and 10 copies of each event being reported.