nimbusGo panel guide: Tyco Fireclass/MX/MZX/Zettler
Equipment required
From Nimbus
- A nimbusGo device connected to Nimbus Digital App.
- A 2M Adapter Lead (part no 201-101-01).
- A Tyco MX, MZX & Fireclass Panel Adapter (part no 201-108-01).
From the panel manufacturer/3rd party
- Consys v25.0 or later.
Panel configuration
- Set the panel baud rate to 9600
- Set Comm Port 1 to Printer or TPI mode. Note that this must match that of the equipment in the Nimbus Web Portal to enable communications.
- When configured as a printer, comm 1 outputs 2 lines of ASCII data
- When configured as a TPI, comm port 1 outputs 3 lines of ASCII data
- Ensure Paper Width is set to Standard (80)
- Enable Quiescent Logging
Panel connection
Connect nimbusGo to the RS232 connections on the interface via the 2M Adapter Lead and Tyco MX, MZX & Fireclass Panel Adapter.
You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Digital App.
Learn more: Conducting a service visit
Certain models and configurations of Tyco panels will not ouput events while in Test Mode. Please consider how you can conduct testing in normal operation as a workaround, or speak to the panel manufacturer for more information.