nimbusGo panel guide: Ziton ZP2

Equipment required

From Nimbus

From the panel manufacturer/3rd party

  • Ziton 2010-2-232-KIT Addressable Fire Panel Accessory – RS232 Kit.

 

    Panel configuration

    • Select [Panel Setup]
    • Select [Printer Config]
    • Select [Ext. Printer]
    • Select [Ext. Printer Config]
      • Used enabled
      • ProtMd disabled
      • NWEvents enabled 
      • Alarm enabled
      • Fault enabled 
      • Cond enabled 
      • StatCh enabled 
      • BaudR 19200

     

    Panel connection

    Connect nimbusGo via the 2m Adapter Lead, Multi Panel (9 Pin Female D) Panel Adapter and Ziton 2010-2-232-KIT Addressable Fire Panel Accessory – RS232 Kit.

    You will now see the panel LED on nimbusGo turn green, and "good" panel comms will be indicated in Nimbus Engineer.